EDApower Showroom
Av. Chile España 414 | Ñuñoa – Santiago de Chile
Data Center construido en un contenedor marítimo de 10 pies
Data Center construido en un contenedor marítimo de 20 pies
UPS fabricadas especialmente parael respaldo de energía de maquinaria industrial
Garantía UPS: 1 AÑO
Garantía Baterías: 1 AÑO
Características
Peso: 508 Kg
Ancho: 80 cm
Alto: 180 cm
Largo: 80 cm
MODEL | GTI33-40 |
CAPACITY | 40KVA / 36KW |
INPUT | |
Rectifier Type | 6 pulse |
Main Input and Bypass Input | Supports dual inputs |
Nominal Voltage | 380VAC/400VAC/415VAC |
Acceptable Voltage Range | 304VAC ~ 456VAC |
Frequency | 50Hz/60Hz ± 10% |
TVSS | 40kA |
BYPASS | |
Nominal Voltage | 380VAC/400VAC/415VAC |
Input Voltage Range | 285VAC ~ 475VAC |
BATTERY | |
Battery Voltage | 384 VDC (Adjustable) |
Cold Start | Yes |
OUTPUT | |
Power Factor | 0.9, customized up to 1.0 |
Nominal Output Voltage | 380VAC/400VAC/415VAC |
Output Voltage Regulation | ±1% |
Frequency | 50Hz/60Hz ± 1% |
Overload Capability | 110% continuous running; 125% for 10 min; >150% for 1 min |
PHYSICAL | |
IP Protection | IP31 (default), IP42 (optional) |
Dimensions,DxWxH(mm) | 800 x 800 x 1800 |
Net Weight (Kgs) | 508 |
ENVIRONMENT | |
Operating Temperature | 0~ 40°C |
Storage Temperature | -25°C ~ 55°C |
Humidity | 0~95% (non-condensing) |
Altitude | 1000m |
MANAGEMENT | |
Modbus RS-232/RS485 | Supports Windows® family, Linux and MAC |
Dry Contacts | 5 outputs and 4 inputs |
Optional SNMP | Power management from SNMP manager and web browser |
STANDARD | |
Safety | IEC62040-1-2017 |
EMC Immunity | IEC61000-4-5 |
EMC Emissions | IEC62040-2-2018 |
Approvals | CE / CB/ Conformance testing / EMC / ROHS2 / Reach / YDT1095-2018 |
Av. Chile España 414 | Ñuñoa – Santiago de Chile